fulltextpubmed· Full Text· item 33190858

Editor—During the severe acute respiratory syndrome coronavirus-1 epidemic, healthcare workers involved in aerosol-generating procedures, such as tracheal intubation or bronchoalveolar lavage, were at increased risk of becoming infected.1 For the current coronavirus disease 2019 pandemic caused by severe acute respiratory syndrome coronavirus-2 (SARS-CoV-2), several international guideline committees have recommended that these procedures be performed in airborne isolation rooms.2, 3, 4 These rooms typically have a negative pressure relative to the adjacent hallway and a relatively high air exchange rate. However, because they are limited in most hospitals, it is inevitable that, in the context of a pandemic, aerosol-generating procedures in SARS-CoV-2-infected patients take place in other hospital environments, such as operating theatres or general ward rooms.

fulltextpubmed· Full Text· item 33190858

e adjacent hallway and a relatively high air exchange rate. However, because they are limited in most hospitals, it is inevitable that, in the context of a pandemic, aerosol-generating procedures in SARS-CoV-2-infected patients take place in other hospital environments, such as operating theatres or general ward rooms. Ventilation system properties differ in various hospital settings, and this could influence aerosol behaviour, potentially compromising healthcare worker safety. For instance, ventilation systems in operating theatres are not designed for airborne isolation, but to protect the surgical field from contamination using a positive-pressure system. In ward rooms, air exchange rates are much lower than in an airborne isolation room or operating theatre. To our knowledge, no previous study has compared the relative influence of room pressure and air exchange rate on aerosol behaviour in different hospital settings. We aimed to quantify this to identify potential risks associated with different working environments. The results could guide specific recommendations that may help in choosing optimal working environments to protect healthcare workers performing aerosol-generating procedures.

fulltextpubmed· Full Text· item 33190858

behaviour in different hospital settings. We aimed to quantify this to identify potential risks associated with different working environments. The results could guide specific recommendations that may help in choosing optimal working environments to protect healthcare workers performing aerosol-generating procedures. We performed a simulated aerosol-generating procedure on six different single-patient hospital rooms (Supplementary data A1–A5) with varying air exchange rates (1–91 change [s] h−1) and pressure gradient towards the adjacent hallway (P room–P hallway; measured with a needle micromanometer [AccuBalance® 8380; TSI, Shoreview, MN, USA]). One of the rooms with a low air exchange rate was equipped with an air purification unit (City Touch™; Camfil, Stockholm, Sweden) recirculating 600 m3 h−1 through an efficiency particulate air filter with a 99.5% particle removal efficiency to improve air exchange rate. Aerosols were dispersed from a test fluid (Durasyn® 164/Emery; INEOS, London, UK) using a nebuliser (ATM 226; Topas GmbH, Dresden, Germany) positioned at the head end of the bed (1 m above ground level). Two particle counters (SOLAIR 3100; Lighthouse, Boven-Leeuwen, the Netherlands), sampling air 1.5 m above ground level, were placed in the periphery of the room and in the hallway next to the closed door. All equipment was remotely operated to avoid room disturbance; doors remained closed during the entire measurement sequence. The study protocol measurements consisted of a 15 min baseline and 15 min of particle dispersal followed by a washout time recording of 60 min.

fulltextpubmed· Full Text· item 33190858

he room and in the hallway next to the closed door. All equipment was remotely operated to avoid room disturbance; doors remained closed during the entire measurement sequence. The study protocol measurements consisted of a 15 min baseline and 15 min of particle dispersal followed by a washout time recording of 60 min. Data were stored digitally and processed offline (MATLAB R2018b; MathWorks Inc., Natick, MA, USA). After triplicate measures on each hospital room, data were synchronised and particle concentration counts were averaged per minute. Because SARS-CoV-2 aerosols appear in two peak concentrations with aerodynamic diameters of 0.25–1.0 and >2.5 μm, we analysed particle size ≥0.5 μm to assess room ventilation efficacy.5 In all situations, the baseline aerosol concentration was 0–0.6 × 106 m−3, which increased to 10–92 × 106 and 0.2–10 × 106 m−3 after aerosol dispersal in the hospital rooms and in the hallway, respectively. Aerosol washout was modelled as the fitted natural exponential decay function (R 2 >0.95 for all situations), as proposed by the US Centers for Disease Control and Prevention (Supplementary data A6).6

fulltextpubmed· Full Text· item 33190858

sed to 10–92 × 106 and 0.2–10 × 106 m−3 after aerosol dispersal in the hospital rooms and in the hallway, respectively. Aerosol washout was modelled as the fitted natural exponential decay function (R 2 >0.95 for all situations), as proposed by the US Centers for Disease Control and Prevention (Supplementary data A6).6 We classified the six rooms according to their ventilation system properties with air exchange rate (high vs low) and pressure gradient towards the hallway (positive vs neutral vs negative). Results are summarised in Table 1 and in the Supplementary data. There was considerable variation between the rooms with the 99% removal time of aerosols ranging between 7 and 307 min depending on air exchange rate. On the room with the lowest air exchange rate, the addition of an air purification unit improved air exchange rate from 1 to 11 change(s) h−1 and 99% removal time of aerosols from 307 to 47 min. Aerosol distribution to the hallway, calculated as the ratio of areas under the curve (AUChallway/AUCroom), was associated with pressure hierarchy. We found significant distribution (4–15%) on positive-pressure rooms, detectable distribution (1%) on neutral-pressure rooms, and unmeasurable (0%) on negative-pressure rooms. For each pressure gradient, higher ventilation rates seemed to reduce hallway exposure (Supplementary data A7).Table 1Classification of room pressure gradients, ventilation system settings, and aerosol clearances. Detailed descriptive information on included rooms and their ventilation system settings. Rooms were classified according to their ventilation system properties with air exchange rate (high vs low) and pressure gradient towards the hallway (positive vs neutral vs negative). The main outcome measures for the study were aerosol clearance, expressed as the time necessary to remove 99% of aerosols after a simulated aerosol-generating procedure and relative hallway exposure, expressed as the ratio between hallway and room exposure. Lower 99% contaminant removal times were found on rooms with higher air exchange rates. We found significant aerosol distribution (4–15%) in positive-pressure rooms, detectable distribution (1%) in neutral-pressure rooms, and unmeasurable distribution (0%) in negative-pressure rooms. Higher ventilation rates seemed to reduce hallway exposure.

fulltextpubmed· Full Text· item 33190858

moval times were found on rooms with higher air exchange rates. We found significant aerosol distribution (4–15%) in positive-pressure rooms, detectable distribution (1%) in neutral-pressure rooms, and unmeasurable distribution (0%) in negative-pressure rooms. Higher ventilation rates seemed to reduce hallway exposure. APU, air purification unit; AUC, area under the curve.Table 1Positive-pressure gradientNo pressure gradientNegative-pressure gradientLow ventilation rateHigh ventilation rateLow ventilation rateHigh ventilation rateLow ventilation rateHigh ventilation rateDescriptive data Included rooms Room typeDelivery roomStandard operating theatreWard roomWard room+APUAirborne isolation roomNegative-pressure operating theatre Room volume (m3)68129666637129 Anteroom (if present; m3)15———9—Ventilation system settings Pressure hierarchy (Proom–Phallway; Pa)92000–15–2 Exchanged air per hour (m3 h−1)16911 2877169928611 680 Air exchange rate (changes h−1)388111891Aerosol concentration of ≥0.5 μm Room Baseline (106 m−3)0.200.60.20.10 Peak (106 m−3)851392826310 Cumulative exposure (AUC 106)81.31.9414253.235.71.23Hallway Baseline (106 m−3)0.30.10.20.20.10.2 Peak (106 m−3)100.41.00.50.20.2 Cumulative exposure (AUC 106)12.40.080.750.010.040.00Main outcome Aerosol clearance and distribution 99% Contaminant removal time (min)93730747387 Hallway exposure, relative to room exposure (%)1541000

fulltextpubmed· Full Text· item 33190858

exposure (AUC 106)81.31.9414253.235.71.23Hallway Baseline (106 m−3)0.30.10.20.20.10.2 Peak (106 m−3)100.41.00.50.20.2 Cumulative exposure (AUC 106)12.40.080.750.010.040.00Main outcome Aerosol clearance and distribution 99% Contaminant removal time (min)93730747387 Hallway exposure, relative to room exposure (%)1541000 Classification of room pressure gradients, ventilation system settings, and aerosol clearances. Detailed descriptive information on included rooms and their ventilation system settings. Rooms were classified according to their ventilation system properties with air exchange rate (high vs low) and pressure gradient towards the hallway (positive vs neutral vs negative). The main outcome measures for the study were aerosol clearance, expressed as the time necessary to remove 99% of aerosols after a simulated aerosol-generating procedure and relative hallway exposure, expressed as the ratio between hallway and room exposure. Lower 99% contaminant removal times were found on rooms with higher air exchange rates. We found significant aerosol distribution (4–15%) in positive-pressure rooms, detectable distribution (1%) in neutral-pressure rooms, and unmeasurable distribution (0%) in negative-pressure rooms. Higher ventilation rates seemed to reduce hallway exposure. APU, air purification unit; AUC, area under the curve.

fulltextpubmed· Full Text· item 33190858

e rates. We found significant aerosol distribution (4–15%) in positive-pressure rooms, detectable distribution (1%) in neutral-pressure rooms, and unmeasurable distribution (0%) in negative-pressure rooms. Higher ventilation rates seemed to reduce hallway exposure. APU, air purification unit; AUC, area under the curve. These results highlight the importance of ventilation system settings on aerosol clearance and distribution in various in-hospital settings. In this study, aerosols remained airborne for more than 5 h in a room with low ventilation rate. These rooms should be considered ‘contaminated’ for extended durations after aerosol-generating procedures have been performed in SARS-CoV-2-infected patients, as it has been shown that airborne SARS-CoV-2 remains viable for at least 3 h.7 Addition of a recirculating air purification unit in these rooms improved aerosol washout dramatically; this could be a simple and inexpensive solution to improve safety for healthcare workers.

fulltextpubmed· Full Text· item 33190858

een performed in SARS-CoV-2-infected patients, as it has been shown that airborne SARS-CoV-2 remains viable for at least 3 h.7 Addition of a recirculating air purification unit in these rooms improved aerosol washout dramatically; this could be a simple and inexpensive solution to improve safety for healthcare workers. Air exchange rate in the operating theatre was very high, and therefore, the time needed to remove 99% of all aerosols was very short. Although this may vary between hospitals,8 in our setting, aerosol distribution to the hallway could not be neglected for a positive-pressure gradient. Whereas reduced hallway exposure was found in neutral- and negative-pressure environments, healthcare workers in the room benefit most from high air exchange rates to reduce the amount of aerosols quickly. It is important to assess the local situation when deciding on the best location for aerosol-generating procedures in SARS-CoV-2-infected patients.